Continuously Corrugated Welded Cable – CCW®
133% EPR Insulation – PVC Jacket
105°C – UL Type MC-HL or MV-105
15kV – 3-Conductor – Shielded
133% EPR Insulation – PVC Jacket
105°C – UL Type MC-HL or MV-105
15kV – 3-Conductor – Shielded
Download PDF
Email PDF
Construction | |
---|---|
Conductor |
|
Extruded Strand Shield |
|
Insulation |
|
Extruded Insulation Shield |
|
Grounding Conductor |
|
Shield |
|
Armor |
|
Jacket |
|
Applications:
- For use in feeders and branch circuits in industrial power distribution systems per NEC articles 328 and 330
- Approved for Classes I, II and III, Divisions 1 and 2; and Class I, Zones 1 and 2, hazardous locations covered under NEC Articles 501, 502, 503 and 505
- Installed on metal racks, troughs, in raceways, in cable trays or secured to supports spaced no more than 6 feet apart
- Installed in both exposed and concealed work, wet or dry locations, directly buried or embedded in concrete
Features:
- Cable meets cold impact at -40°C
- 105°C continuous operating temperature, wet or dry
- 140°C emergency rating
- 250°C short circuit rating
Standards:
- UL 1072
- UL 1569
- UL 2225
- UL 1309
- IEEE 1202 available upon request
Note: The data shown are approximate and subject to standard industry and manufacturer tolerances. Please verify specific requirements with your Omni Cable account manager.