MEDIUM VOLTAGE POWER CABLE
15kV
URD
XLP Insulation
Download PDF

CONSTRUCTION
Conductor: -A- Stranded Compressed (-A for Aluminum, -C for Copper) Class B stranding
Conductor Shield: - Extruded semiconducting thermoset polymer
Insulation: - Extruded tree retardant crosslinked polyethylene
Insulation Shield: - Extruded semiconducting thermoset polymer
Concentric Neutral: - Bare copper concentric neutral wires
Outer Jacket: - Encapsulated linear low density polyethylene
Standards:
- ICEA S-94-649
- AEIC CS8-00
- PECO spec 125-P-18
Part # AWG No. of Strands Nominal Insulation Thickness Neutral AWG Diameter Over Insulation Nominal O.D. Lbs./M’
MUP10201-A 2 7 .175" 10X14 .752" .990" 482
MUP10201-C 2 7 .175" 16X14 .700" 1.06" 680