600 Volts, Copper Conductor
Single Conductor Central Office Power Wire and Cable
Class B Stranded with Braid
CSA Approved, Non-Halogen Insulation
Single Conductor Central Office Power Wire and Cable
Class B Stranded with Braid
CSA Approved, Non-Halogen Insulation
Download PDF
Email PDF
Construction | |
---|---|
Conductors |
|
Insulation |
|
Separator |
|
Covering |
|
Standards:
- UL Listed RHH/ST1
- FT4- Flame Test
- VW-1
- ASTM B-33
- Physical and Electrical tests in accordance with UL standard 44 requirements
- CSA AWM I B 105°C
Part # | AWG | Stranding | Insulation Min. Avg. Wall (mils) | Nominal O.D. over Insulation | Nom. O.D. Overall | Max D.C. Res. @ 20°C (Ohms/M) | Lbs./M' |
---|---|---|---|---|---|---|---|
TF314-XX | 14 | 7/.0242 | 45 | .165″ | .200″ | 2.730 | 32 |
TF312-XX | 12 | 7/.0305 | 45 | .185″ | .220″ | 1.720 | 42 |
TF310-XX | 10 | 7/.0385 | 45 | .210″ | .250″ | 1.080 | 60 |
TF308-XX | 8 | 7/.0486 | 60 | .270″ | .320″ | .678 | 92 |
TF306-XX | 6 | 7/.0612 | 60 | .305″ | .355″ | .427 | 130 |
TF304-XX | 4 | 7/.0772 | 60 | .350″ | .400″ | .269 | 186 |
TF302-XX | 2 | 7/.0974 | 60 | .410″ | .460″ | .169 | 258 |
TF31/0-XX | 1/0 | 19/.0745 | 80 | .530″ | .585″ | .106 | 439 |
TF32/0-XX | 2/0 | 19/.0837 | 80 | .575″ | .630″ | .084 | 530 |
TF34/0-XX | 4/0 | 19/.1055 | 80 | .680″ | .735″ | .052 | 795 |
TF3350-XX | 350 | 37/.0973 | 95 | .860″ | .915″ | .032 | 1292 |
TF3500-XX | 500 | 37/.1162 | 95 | .990″ | 1.045″ | .022 | 1762 |
TF3750-XX | 750 | 61/.1109 | 110 | 1.200″ | 1.260″ | .0148 | 2647 |
Note: The data shown is approximate and subject to standard industry and manufacturer tolerances.
Insert the color number in the XX location.